菜单
  
    AbstractOutdoor design conditions are important parameters for energy efficiency of buildings. The result of incorrect selection of outdoordesign conditions can be dramatic in view of comfort and energy consumption. In this study, the influence of different outdoor designconditions on air conditioning systems is investigated. For this purpose, cooling loads and capacities of air conditioning equipments for asample building located in Adana, Turkey are calculated using different outdoor design conditions recommended by ASHRAE, the cur-rent design data used in Turkey and the daily maximum dry and wet bulb temperatures of July 21st, which is generally accepted as thedesign day. The cooling coil capacities obtained from the different outdoor design conditions considered in this study are compared witheach other. The cost analysis of air conditioning systems is also performed. It is seen that the selection of outdoor design conditions is avery critical step in calculation of the building cooling loads and design capacities of air conditioning equipments.  2007 Elsevier Ltd. All rights reserved.27896
    Keywords: Weather design data; HVAC system; Cooling load; Cost analysis
    1. IntroductionLocal climatic conditions are important parametersfor the energy efficiency of buildings. Because the energyconsumption in buildings depends on climatic condi-tions and the performance of heating ventilating and airconditioning (HVAC) systems changes with them as well,better design in building HVAC applications that takeaccount of the right climatic conditions will result in bettercomfort and more energy efficient buildings.Outdoor design conditions are weather data informationfor design purposes showing the characteristic features ofthe climate at a particular location. They affect buildingloads and economical design. The result of incorrect selec-tion of outdoor conditions can be dramatic in view ofenergy and comfort. If some very conservative, extreme conditions are taken, uneconomic design and over sizingmay result. If design loads are underestimated, equipmentand system operation will be affected. However, selectingthe correct type of weather data is a difficult problem. Toovercome the problem, Yoshida and Terai [1] constructedan autoregressive moving average (ARMA) type weathermodel by applying a system identification technique tothe original weather data. Li et al. [2] studied climaticeffects on cooling load determination in subtropicalregions. They found that the outdoor climatic conditionsdeveloped for cooling load estimations are less stringentthan the current outdoor design data and approachesadopted by local architectural and engineering practices.Zogou and Stamatelos [3] provided a comparative discus-sion on the effect of climatic conditions on the design opti-mization of heat pump systems and showed that climaticconditions significantly affect the performance of heatpump systems, which should lead to markedly differentstrategies for domestic heating and cooling, if an optimiza-tion is sought on sustainability grounds. Lam [4] studied climatic influences on the energy performance of air condi-tioned buildings and found that the predictions of annualcooling loads, peak cooling loads and annual electricityconsumption differ by up to about 14%. Bulut et al. [5,6]determined new cooling and heating design data for Tur-key. They used the current outdoor design data locally usedand the new data presented in their studies [5,6] in order toevaluate the influence of the weather data set on the heat-ing and cooling load. They found up to 25% and 32% dif-ferences between the cases considered for cooling andheating loads, respectively.Outdoor design conditions corresponding to differentfrequency levels of probability for several locations in theUnited States and around the world are developed by theAmerican Society of Heating, Refrigeration and Air Con-ditioning Engineers, Inc. (ASHRAE) [7]. Weather dataincludes design values of dry bulb temperature with meancoincident wet bulb temperature, design wet bulb tempera-ture with mean coincident dry bulb temperature and designdew point temperature with mean coincident dry bulb tem-perature and corresponding humidity ratio. These designdata are the outdoor conditions that are exceeded duringa specified percentage of time. Warm season temperatureand humidity conditions correspond to annual percentilevalues of 0.4, 1.0 and 2.0. Cold-season conditions are basedon annual percentiles of 99.6 and 99.0. The 0.4%, 1.0% and2.0% annual values of occurrence represent the value thatoccurs or is exceeded for a total of 35 h, 88 h and 175 h,respectively, on average, every year, over the period ofrecord. The selection of frequency as risk level in designconditions depends on the applications. Representing theclimatic design data for several frequencies of occurrencewill also enable designers to consider various operationalpeak conditions.
  1. 上一篇:塑料模具钢英文文献和中文翻译
  2. 下一篇:液压系统的英文文献及中文翻译
  1. 绿色建筑与室内空气质量英文献和中文翻译

  2. 内河运输船舶碰撞与搁浅...

  3. 产业集群与城市化英文文献和中文翻译

  4. 轴承的摩擦与润滑英文文献和中文翻译

  5. 通风空调(暖通空调)风...

  6. 承载力的立足点在斜坡带...

  7. 国际工程项目组织与管理英文文献和参考文献

  8. 酸性水汽提装置总汽提塔设计+CAD图纸

  9. 大众媒体对公共政策制定的影响

  10. 河岸冲刷和泥沙淤积的监测国内外研究现状

  11. java+mysql车辆管理系统的设计+源代码

  12. 十二层带中心支撑钢结构...

  13. 当代大学生慈善意识研究+文献综述

  14. 杂拟谷盗体内共生菌沃尔...

  15. 电站锅炉暖风器设计任务书

  16. 中考体育项目与体育教学合理结合的研究

  17. 乳业同业并购式全产业链...

  

About

751论文网手机版...

主页:http://www.751com.cn

关闭返回